Kewtech KT66ET Multifunction Tester with Earth Test Kit

Product Code: KEWKT66ET

Price
£1119.00 ex. VAT £1342.80 inc. VAT

Available In 3-7 Days


Add To Favourites
Detailed Description

The KT66DL multifunction tester, combined with our ACCES earth spike kit, is the most cost effective way to obtain an instrument that will test TN, TT and independent earthing systems.
The spike kit fits into the KT66DL carry case so everything can be kept together in one place.
The KT66DL comes with CD-ROM software but if you would prefer to download the KEW REPORT software you can do so here…Download Software.

The market's most comprehensive Multifunction Tester complete with an Earth Spike Kit.

  • Includes KT66DL & (ACCESKIT) Earth Spike kit for Earth resistance testing
  • RCD Type B, EV & 6mA
  • Low current 3 & 2 wire loop tests
  • High current 25A 0.001 ohm range

*Important Calibration Information:
This instrument comes complete with the manufacturer’s calibration certificate. Please be aware that these certificates are generic and may also be time lapsed. If you would prefer a personalised full traceable calibration certificate applied to the equipment before dispatch, then please select this option from the drop-down menu above, an additional calibration charge will apply.

Overview:

The KT66DL multifunction tester, combined with our ACCES earth spike kit, is the most cost effective way to obtain an instrument that will test TN, TT and independent earthing systems.

The spike kit fits into the KT66DL carry case so everything can be kept together in one place.

The KT66DL comes with CD-ROM software but if you would prefer to download the KEW REPORT software you can do so here…Download Software.

Key Benefits:

  • Large colour dot matrix screen
  • Established easy to use interface with one rotary dial and four function keys
  • Includes ACCES earth spike kit for earth resistance testing
  • Simultaneous display of L-N, L-N, L-E voltage (TRMS)
  • Max Zs tables for current and old standards
  • Comprehensive RCD function including type EV & B and variable RCD test
  • Three modes of starting a test: single press of the test button, continuous testing and by test button in the test probe
  • Advanced memory - assigns DB, circuit no. ad type of test i.e. Zs or Ze
  • Help display
  • Touch voltage pad with selectable limits
  • Padded neck strap
  • Comes complete with KT66DL, KEWEVSE, soft canvas bag, mains lead, DB leads, remote test probe and software
  • Compatible with optional KEWEVSE adapter for testing EVSE charging points

Key Features:

  • Two high current loop options: 25A 0.001 Ohm resolution & 6A 0.01 Ohm resolution
  • Two low current loop options: 3 wire & 2 wire
  • 55V loop test capability - suitable for 110V CTE systems
  • EVSE loop option
  • RCD - Tests Type AC, ACS, A, AS, F, B, BS & EV
  • EVSE 6mA DC ramp and tripping time test
  • UC - contact voltage test
  • Insulation test function with PI
  • Two continuity tests 200mA & 15mA
  • Surge protection device test
  • Earth resistance 3 & 2 wire options
  • Phase rotation
  • True RMS Voltage measurements 2-600V, mains frequency
  • PAT function including download
  • Advanced memory

    

Kewtech KT63DL Technical Specification
Loop Impedance
Range 20.00/200.0/2000Ω (auto-ranging)
Display range 0.00 - 20.99Ω / 16.0 - 209.9Ω / 160 - 2099Ω
Measuring range 0 – 2000Ω
Accuracy ±2.0%rdg±8dgt
Open-circuit voltage 7 – 14V DC
Test current 200mA test: 200mA or more (2Ω or less)
15mA test: 15mA±3mA (short-circuit)
Note

• Enabled if pre-set NULL value is 9Ω or less.

• Buzzer: Buzzer sounds when measured resistance is 2Ω or less.

Voltage
Range 300.0/600V (Auto-ranging)
Display range Voltage: 2.0 – 314.9V, 240 – 629V
Frequency: 40.0 – 70.0Hz (displayed at 2V or higher)
Measuring.range Voltage: 2 – 600V
Frequency: 45 – 65Hz
Accuracy Voltage: ±2%rdg±4dgt
Frequency: ±0.5%rdg±2dgt
Uc (RCD)
Mains voltage range 100-260V
Range 100V
Display range 0.0 - 104.9V
Measuring range 0 - 100V
Accuracy +5%to+15%rdg ±8dgt 230V
Test current 50 % or less of IΔn
Earth
  Precise measurement Simplified measurement
Range 20.00 / 200.0 / 2000Ω (auto-ranging)
Accuracy 20Ω range; ±2%rdg±0.08Ω
The other ranges: ±2%rdg±3dgt
(Aux. earth resistance: 100Ω)
±2%rdg±0.08Ω
The other ranges: ±2%rdg±3dgt
Output current 20Ω range: approx. 3mA, 200v range: approx. 1.7mA
2000Ω range: approx. 0.7mA Frequency: 825Hz
Phase Rotation
Measuring Range 48 – 600V / 45 - 65Hz
Criteria of judgement Correct sequence: Clockwise symbol and “1, 2, 3” are displayed.
Reversed sequence: Counter-clockwise symbol and “3, 2, 1” are displayed.
Insulation
Rated voltage 100V 250V 500V 1000V SPD (Varistor) 1000V
Range 2.000/20.00/200.0MΩ
auto-ranging
20.00/200.0/1000MΩ
auto-ranging
20.00/200.0/2000MΩ 0 -1000V (increases in 1V steps)
Display range 0.000 - 2.099MΩ 0.00 - 20.99MΩ 0.00 - 20.99MΩ 1049V
1.60 - 20.99MΩ 16.0 - 209.9MΩ 16.0 - 209.9MΩ
16.0 - 209.9MΩ 160 - 1049MΩ 160 - 2099MΩ
Measuring range 0 - 200MΩ 0 - 1000MΩ 0 - 2000MΩ 0 - 1049V
Accuracy 2.000MΩ range: ±2%rdg±6dgt 20.00MΩ range: ±(2%rdg+6dgt), 200.0MΩ range: ±(2%rdg+6dgt) ±5%rdg±5dgt
20.00MΩ range: ±2%rdg±6dgt 1000MΩ range: ±(5%rdg+6dgt) 2000MΩ range: ±(5%rdg+6dgt)
200MΩ range: ±5%rdg±6dgt
Rated meas.
current
1.0 - 1.2mA
at 100kΩ
1.0 - 1.2mA
at 250kΩ
1.0 - 1.2mA
at 500kΩ
1.0 - 1.2mA
at 1MΩ
1.0 mA
Loop
Function LOOP ATT LOOP HIGH
3-Wire L-PE 2-Wire L-PE L-PE0.01ΩRes L-PE0.001ΩRes L-N/L-L
Mains input
voltage range
100 – 260V 50/60Hz
(L-N < 20Ω)
48 – 260V 50/60Hz 100 - 260V 50/60Hz 48 - 260V 50/60Hz
Range LOOP 20.00/200.0/2000Ω (auto-ranging)   20.00/200.0/2000Ω 2.000Ω 20.00Ω
PFC/PSC 2000A/20kA 2000A/20kA (PFC only) 2000A/50kA (PFC only) 2000A/20kA (PSC only) 2000A/20kA (PSC only)
Display range LOOP 0.00 – 20.99Ω
21.0 – 209.9Ω
210 – 2099Ω
0.00 –20.99Ω
21.0 –209.9Ω
210 –2099Ω
0.00 - 20.99Ω
21.0 - 209.9Ω
210 –2099Ω
0.000 - 2.099Ω 0.00-20.99Ω
PFC/PSC 0 – 2099A
2.10 – 20.99kA
0 – 2099A
2.10 – 20.99kA
(PFC only)
0 – 2099A
2.10 – 50.49kA
(PFC only)
0 – 2099A
2.10 – 20.99kA
(PFC only)
0 – 2099A
2.10 – 20.99kA
(PSC only)
Meas. range LOOP 0 – 2000Ω 0 – 2000Ω 0 – 2000Ω 0 – 2Ω 0 – 20
Accuracy LOOP ±(3%rdg+6dgt) ±(3%rdg+10dgt) ±(3%rdg+4dgt) ±(3%rdg+25mΩ) ±(3%rdg+4dgt)
PFC/PSC Depending on the accuracies of voltage and LOOP measurements
Test current @ 230V L-N:6A/60ms
N-PE:10mA (5.3Hz)
L-PE: 15mA 20Ω: 6A/20ms,
200Ω: 0.5A/20ms
2000Ω: 15mA/500ms
25A/20ms 6A/20ms
RCD
Mode Rated residual operating current (mA)(IΔn) Test current Duration
Current (mA) rms Accuracy @230V Meas. time Accuracy
x 1/2 AC G: 10/30/100/300/500/1000 S: 100/300/500 IΔn×1/2 -8% to-2% VAR:-10% to 0% 2000ms Trip Time
±(1%+2ms)
Measuring
time
±3% of FS
A/F G: 10/30/100/300/500 AS:100/300/500 IΔn×1/2 -10% to 0%
B G: 10/30/100/300 S:100/300 IΔn×1/2 -10% to 0%
x 1 AC G:10/30/100/300/500/1000 S: 100/300/500 IΔn +2% to +8% VAR:0% to +10% G:550ms
S:1000ms
A/F G: 10/30/100/300/500 AS:100/300/500 IΔn×1.4 (10mA: IΔn×2) 0% to +10%
B G: 10/30/100/300 S:100/300 IΔn×2 0% to +10%
6 mA DC IΔn 0% to +10% 10.5s  
x 5 AC G: 10/30/100 S: 100 IΔn×5 +2% to +8% VAR:0% to +10% 410ms  
A/F G: 10/30/100 AS: 100 IΔn×5×1.4 0% to +10%
B 10/30 IΔn×2×5 0% to +10%
Ramp
20 to 110%
AC 10/30/100/300/500 S: 100/300/500 IΔn -4% to +4% by 10%
G: 300ms
S: 500ms
Measuring
time
±3% of FS
A/F G: 10/30/100/300/500 AS:100/300/500 IΔn×1.4 (10mA:IΔn×2) -10% to +10%
B G: 10/30/100/300 S: 100/300 IΔn×2 -10% to +10% by 2% /150ms
Ramp EV 30 to 100% 6 mA DC IΔn -10% to +10% by 2% / 500ms  
General Specification
Applicable Standards IEC 61010-1 CATIII (600V) CATIV (300V) pollution degree 2, IEC 61010 -Tester , -2-030, -2-034,
IEC61557-1,2,3,4,5,6,7,10, IEC 60529 IP40, EN 61326-2-2 (EMC)
Dimensions & Weight 136 (L) x 235(W) x 114 (D) mm, 1300g including batteries (8 x AA / LR6)
UK Mainland Order by 2pm for Next Day Delivery*
Under £25.00 £4.50
Over £25.00 FREE

UK Highlands & Islands Order by 2pm for Next Day Delivery*
Under £80.00 £15.00
Over £80.00 FREE