Product Code: KEWKT66ET
Available In 3-7 Days
The KT66DL multifunction tester, combined with our ACCES earth spike kit, is the most cost effective way to obtain an instrument that will test TN, TT and independent earthing systems.
The spike kit fits into the KT66DL carry case so everything can be kept together in one place.
The KT66DL comes with CD-ROM software but if you would prefer to download the KEW REPORT software you can do so here…Download Software.
The market's most comprehensive Multifunction Tester complete with an Earth Spike Kit.
*Important Calibration Information:
This instrument comes complete with the manufacturer’s calibration certificate. Please be aware that these certificates are generic and may also be time lapsed. If you would prefer a personalised full traceable calibration certificate applied to the equipment before dispatch, then please select this option from the drop-down menu above, an additional calibration charge will apply.
The KT66DL multifunction tester, combined with our ACCES earth spike kit, is the most cost effective way to obtain an instrument that will test TN, TT and independent earthing systems.
The spike kit fits into the KT66DL carry case so everything can be kept together in one place.
The KT66DL comes with CD-ROM software but if you would prefer to download the KEW REPORT software you can do so here…Download Software.
Kewtech KT63DL Technical Specification | |
Loop Impedance | |
Range | 20.00/200.0/2000Ω (auto-ranging) |
Display range | 0.00 - 20.99Ω / 16.0 - 209.9Ω / 160 - 2099Ω |
Measuring range | 0 – 2000Ω |
Accuracy | ±2.0%rdg±8dgt |
Open-circuit voltage | 7 – 14V DC |
Test current | 200mA test: 200mA or more (2Ω or less) 15mA test: 15mA±3mA (short-circuit) |
Note |
• Enabled if pre-set NULL value is 9Ω or less. • Buzzer: Buzzer sounds when measured resistance is 2Ω or less. |
Voltage | |
Range | 300.0/600V (Auto-ranging) |
Display range | Voltage: 2.0 – 314.9V, 240 – 629V |
Frequency: 40.0 – 70.0Hz (displayed at 2V or higher) | |
Measuring.range | Voltage: 2 – 600V |
Frequency: 45 – 65Hz | |
Accuracy | Voltage: ±2%rdg±4dgt |
Frequency: ±0.5%rdg±2dgt |
Uc (RCD) | |
Mains voltage range | 100-260V |
Range | 100V |
Display range | 0.0 - 104.9V |
Measuring range | 0 - 100V |
Accuracy | +5%to+15%rdg ±8dgt 230V |
Test current | 50 % or less of IΔn |
Earth | ||
Precise measurement | Simplified measurement | |
Range | 20.00 / 200.0 / 2000Ω (auto-ranging) | |
Accuracy | 20Ω range; ±2%rdg±0.08Ω The other ranges: ±2%rdg±3dgt (Aux. earth resistance: 100Ω) |
±2%rdg±0.08Ω The other ranges: ±2%rdg±3dgt |
Output current | 20Ω range: approx. 3mA, 200v range: approx. 1.7mA | |
2000Ω range: approx. 0.7mA Frequency: 825Hz |
Phase Rotation | |
Measuring Range | 48 – 600V / 45 - 65Hz |
Criteria of judgement | Correct sequence: Clockwise symbol and “1, 2, 3” are displayed. |
Reversed sequence: Counter-clockwise symbol and “3, 2, 1” are displayed. |
Insulation | |||||
Rated voltage | 100V | 250V | 500V | 1000V | SPD (Varistor) 1000V |
Range | 2.000/20.00/200.0MΩ auto-ranging |
20.00/200.0/1000MΩ auto-ranging |
20.00/200.0/2000MΩ | 0 -1000V (increases in 1V steps) | |
Display range | 0.000 - 2.099MΩ | 0.00 - 20.99MΩ | 0.00 - 20.99MΩ | 1049V | |
1.60 - 20.99MΩ | 16.0 - 209.9MΩ | 16.0 - 209.9MΩ | |||
16.0 - 209.9MΩ | 160 - 1049MΩ | 160 - 2099MΩ | |||
Measuring range | 0 - 200MΩ | 0 - 1000MΩ | 0 - 2000MΩ | 0 - 1049V | |
Accuracy | 2.000MΩ range: ±2%rdg±6dgt | 20.00MΩ range: ±(2%rdg+6dgt), 200.0MΩ range: ±(2%rdg+6dgt) | ±5%rdg±5dgt | ||
20.00MΩ range: ±2%rdg±6dgt | 1000MΩ range: ±(5%rdg+6dgt) | 2000MΩ range: ±(5%rdg+6dgt) | |||
200MΩ range: ±5%rdg±6dgt | |||||
Rated meas. current |
1.0 - 1.2mA at 100kΩ |
1.0 - 1.2mA at 250kΩ |
1.0 - 1.2mA at 500kΩ |
1.0 - 1.2mA at 1MΩ |
1.0 mA |
Loop | ||||||
Function | LOOP ATT | LOOP HIGH | ||||
3-Wire L-PE | 2-Wire L-PE | L-PE0.01ΩRes | L-PE0.001ΩRes | L-N/L-L | ||
Mains input voltage range |
100 – 260V 50/60Hz (L-N < 20Ω) |
48 – 260V 50/60Hz | 100 - 260V 50/60Hz | 48 - 260V 50/60Hz | ||
Range | LOOP | 20.00/200.0/2000Ω (auto-ranging) | 20.00/200.0/2000Ω | 2.000Ω | 20.00Ω | |
PFC/PSC | 2000A/20kA | 2000A/20kA (PFC only) | 2000A/50kA (PFC only) | 2000A/20kA (PSC only) | 2000A/20kA (PSC only) | |
Display range | LOOP | 0.00 – 20.99Ω 21.0 – 209.9Ω 210 – 2099Ω |
0.00 –20.99Ω 21.0 –209.9Ω 210 –2099Ω |
0.00 - 20.99Ω 21.0 - 209.9Ω 210 –2099Ω |
0.000 - 2.099Ω | 0.00-20.99Ω |
PFC/PSC | 0 – 2099A 2.10 – 20.99kA |
0 – 2099A 2.10 – 20.99kA (PFC only) |
0 – 2099A 2.10 – 50.49kA (PFC only) |
0 – 2099A 2.10 – 20.99kA (PFC only) |
0 – 2099A 2.10 – 20.99kA (PSC only) |
|
Meas. range | LOOP | 0 – 2000Ω | 0 – 2000Ω | 0 – 2000Ω | 0 – 2Ω | 0 – 20 |
Accuracy | LOOP | ±(3%rdg+6dgt) | ±(3%rdg+10dgt) | ±(3%rdg+4dgt) | ±(3%rdg+25mΩ) | ±(3%rdg+4dgt) |
PFC/PSC | Depending on the accuracies of voltage and LOOP measurements | |||||
Test current @ 230V | L-N:6A/60ms N-PE:10mA (5.3Hz) |
L-PE: 15mA | 20Ω: 6A/20ms, 200Ω: 0.5A/20ms 2000Ω: 15mA/500ms |
25A/20ms | 6A/20ms |
RCD | ||||||
Mode | Rated residual operating current (mA)(IΔn) | Test current | Duration | |||
Current (mA) rms | Accuracy @230V | Meas. time | Accuracy | |||
x 1/2 | AC | G: 10/30/100/300/500/1000 S: 100/300/500 | IΔn×1/2 | -8% to-2% VAR:-10% to 0% | 2000ms | Trip Time ±(1%+2ms) Measuring time ±3% of FS |
A/F | G: 10/30/100/300/500 AS:100/300/500 | IΔn×1/2 | -10% to 0% | |||
B | G: 10/30/100/300 S:100/300 | IΔn×1/2 | -10% to 0% | |||
x 1 | AC | G:10/30/100/300/500/1000 S: 100/300/500 | IΔn | +2% to +8% VAR:0% to +10% | G:550ms S:1000ms |
|
A/F | G: 10/30/100/300/500 AS:100/300/500 | IΔn×1.4 (10mA: IΔn×2) | 0% to +10% | |||
B | G: 10/30/100/300 S:100/300 | IΔn×2 | 0% to +10% | |||
6 mA DC | IΔn | 0% to +10% | 10.5s | |||
x 5 | AC | G: 10/30/100 S: 100 | IΔn×5 | +2% to +8% VAR:0% to +10% | 410ms | |
A/F | G: 10/30/100 AS: 100 | IΔn×5×1.4 | 0% to +10% | |||
B | 10/30 | IΔn×2×5 | 0% to +10% | |||
Ramp 20 to 110% |
AC | 10/30/100/300/500 S: 100/300/500 | IΔn | -4% to +4% | by 10% G: 300ms S: 500ms |
Measuring time ±3% of FS |
A/F | G: 10/30/100/300/500 AS:100/300/500 | IΔn×1.4 (10mA:IΔn×2) | -10% to +10% | |||
B | G: 10/30/100/300 S: 100/300 | IΔn×2 | -10% to +10% | by 2% /150ms | ||
Ramp EV 30 to 100% | 6 mA DC | IΔn | -10% to +10% | by 2% / 500ms |
General Specification | |
Applicable Standards | IEC 61010-1 CATIII (600V) CATIV (300V) pollution degree 2, IEC 61010 -Tester , -2-030, -2-034, IEC61557-1,2,3,4,5,6,7,10, IEC 60529 IP40, EN 61326-2-2 (EMC) |
Dimensions & Weight | 136 (L) x 235(W) x 114 (D) mm, 1300g including batteries (8 x AA / LR6) |
UK Mainland | Order by 2pm for Next Day Delivery* |
---|---|
Under £25.00 | £4.50 |
Over £25.00 | FREE |
UK Highlands & Islands | Order by 2pm for Next Day Delivery* |
---|---|
Under £80.00 | £15.00 |
Over £80.00 | FREE |
Price £35.94 £29.95
Available In 3-7 Days
Price £299.94 £249.95
Available In 3-7 Days
Price £0.19 £0.16
In Stock